Historical

CSA C22.2 No. 96-2013

C22.2 NO. 96-13 - Portable power cables


Preface

This is the tenth edition of CSA C22.2 No. 96, Portable power cables, one of a series of Standards issued by CSA Group under the Canadian Electrical Code, Part II. It supersedes the previous editions, published in 2009, 2003, 1998, 1992, 1989, 1974, 1964, 1958, and 1951.

Scope

1.1
This Standard specifies construction and testing requirements for portable power cables normally used in applications where the cables are subject to frequent flexing and where installation is in accordance with CSA M421 and/or the Canadian Electrical Code, Part I.

1.2
The cable constructions specified in Clauses 5 to 9 and Clauses 12 to 15 of this Standard are suitable for use at a maximum conductor temperature of 90 C under normal operating conditions in wet or dry locations, outdoors or in underground mines, and in rugged environments. The special cable constructions described in Clauses 10 and 11 are suitable for use at a maximum conductor temperature of 105 C.

1.3
This Standard does not specify all types, sizes, and voltage ratings of portable power cables that can be required for particular applications.

1.4
This Standard specifies the following categories of cables:

Clause   Category

5              Thermoset and PUR multiconductor round cables for mining and general applications rated over 2 kV and up to 35 kV
                Types: SHD, SHD-BGC (balanced ground check), SHD-GC,

6              Thermoset and PUR multiconductor round cables for mining and general applications rated up to 2 kV
                Types: W, G, G-BGC (balanced ground check), G-GC, SHC-GC, SHD, SHD-BGC (balanced ground check), SHD-GC

7              Thermoset and PUR single-conductor cables for mining and general applications rated up to 35 kV
                Types: W, SH

8              Thermoset two-and three-conductor flat cables for mining and general applications rated up to 2 kV - suitable for underground applications only
                Types: G, G-GC, W

9              Thermoset three-conductor round cables with a central bonding (grounding) conductor for underground coal mining applications rated up to 5 kV
                Types: SHD-PCG

10             Arc-welding cable

11             Single-conductor portable power cable rated 600 V
                 Types: PPC, PPC/TPE

12             Single and multiconductor portable power cables for general applications rated up to 2 kV
                 Types: PPC, PPC/TPE

13             Flexible multiconductor cable for use with cranes and hoists rated 600 V (festoon cable)

14             Variable frequency drive cable, multiconductor, round, for mining and general applications rated up to 15 kV
                 Types: VFD, VFD-GC, VFD-BGC (balanced ground check)

15             DLO (diesel locomotive) cable, single conductor, used for portable and general permanent applications rated 2 kV

1.5
In this Standard, shall is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; should is used to express a recommendation or that which is advised but not required; and may is used to express an option or that which is permissible within the limits of the standard.

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.

Notes to tables and figures are considered part of the table or figure and may be written as requirements.

Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.

1.6
The values given in SI units are the units of record for the purposes of this Standard. The values given in parentheses are for information and comparison only.