Historical

ANSI/ASHRAE 52.2-2007

Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size


2.1 This standard describes a method of laboratory testing to measure the performance of general ventilation air-cleaning devices.
2.2 The method of testing measures the performance of aircleaning devices in removing particles of specific diameters as the devices become loaded by standardized loading dust fed at intervals to simulate accumulation of particles during service life. The standard defines procedures for generating the aerosols required for conducting the test. The standard also provides a method for counting airborne particles of 0.30 to 10 µm in diameter upstream and downstream of the air-cleaning device in order to calculate removal efficiency by particle size.
2.3 This standard also establishes performance specifications for the equipment required to conduct the tests, defines methods of calculating and reporting the results obtained from the test data, and establishes a minimum efficiency reporting system that can be applied to air-cleaning devices covered by this standard.


CONTENT PROVIDER
American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. [ashrae]

Others Also Bought
Ventilation for Acceptable Indoor Air Quality (Includes Errata sheet and Interpretation 02 to ANSI/ASHRAE Standard ...
Thermal Environmental Conditions for Human Occupancy
Energy Standard for Buildings Except Low-Rise Residential Buildings, I-P Edition
Included in Packages
This standard is not included in any packages.
Document History
Revised By:
Amendments & Corrections
We have no amendments or corrections for this standard.